3516C (50 Hz) with Upgradeable Package
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
-
Generator Set Specifications
-
- Standby Rating
- 2750 kVA
- Prime Power Rating
- 2500 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
- Voltage
- 380 to 11000 volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Mission Critical, Prime
- Maximum Rating
- 2750 kVA
- Minimum Rating
- 2500 kVA
-
Engine Specifications
-
- Engine Model
- 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
- Bore
- 6.69in
- Stroke
- 8.46in
- Displacement
- 4765in
- Compression Ratio
- 14:01
- Aspiration
- TA
- Fuel System
- Electronic unit injection
- Governor Type
- Adem™3
-
Generator Set Dimensions
-
- Length - Maximum
- 228.3in
- Width - Maximum
- 75.9in
- Height - Maximum
- 80.7in
- Dry Weight - Genset (maximum)
- 32404lb
Standard Equipment:
-
Air Inlet System
-
- Air cleaner
- Single element canister type with service indicator
-
Control Panel
-
- RPM
- Engine cycle crank
- Failure to start (overcrank)
- Warning/shutdown with common LED indication of shutdowns for:
- Speed adjust
- True RMS AC metering, 3-phase, +/-2% accuracy
- Accessory module data link
- Overcurrent (50/51)
- DC volts
- Controls:
- Generator phase sequence
- Low oil pressure
- 2 Programmable digital outputs
- Reverse power (kW) (32)
- Low coolant level
- Operating hours
- Frequency (Hz)
- kVAr-hr (total)
- kVA (per phase, average & percent)
- Lamp test
- Over/under frequency (81 o/u)
- 6 programmable digital inputs
- 2 Programmable relay outputs (Form C)
- 24 Volt DC operation
- Customer data link (Modbus RTU)
- EMCP 4 Genset controller
- Volts (L-L & L-N)
- High coolant temperature
- Alarm acknowledge
- Oil pressure (psi, kPa or bar)
- 4 Programmable relay outputs (Form A)
- Overspeed
- EMCP4.2B controller includes:
- Engine cool-down timer
- Panel lights
- kW (per phase, average & percent)
- Low coolant temperature
- Over/under voltage (27/59)
- Serial annunciator module data link
- Generator mounted - rear facing
- Communications:
- kVAr (per phase, average & percent)
- Digital indication for:
- Text alarm/event descriptions
- EMCP 4.2B
- Coolant temperature
- Emergency stop pushbutton
- Programmable protective relaying functions:
- kW-hr (total)
- Reverse reactive power (kVAr) (32RV)
- Amps (per phase & average)
- Environmental sealed front face
- Power factor (per phase & average)
-
Exhaust
-
- Exhaust flange outlet
-
Fuel
-
- Primary fuel filter with integral water separator
-
Generator
-
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
-
Power Termination
-
- Busbar
-
Starting/charging
-
- Heavy duty starting system
- Charging alternator
-
Cooling System
-
- Fan and belt guards
- Coolant drain line with valve
- JWAC
- Caterpillar extended life coolant
- Coolant level sensors
- Radiator fan and fan drive
-
Cooling
-
- Package mounted radiator
-
Exhaust System
-
- Flanged faced outlet(s)
- Dry exhaust manifold
-
Fuel System
-
- Flexible fuel lines - shipped loose
- Fuel priming pump
- Fuel cooler; not included with packages without radiator
- Secondary fuel filters
-
Generators And Attachments
-
- NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby).
- Busbar connections, top center mounted, top cable entry
- Random wound
- 6 Lead
- Winding temperature detectors
- IEC standard hole pattern
- Internal excitation (IE)
- 3 phase brushless, Salient pole
- Generator set packages include Caterpillar's digital voltage regulator (CDVR). CDVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
-
Governing System
-
- ADEM III
-
Literature
-
- English
-
Lube System
-
- Gear type lube oil pump
- Integral lube Oil cooler
- Fumes disposal
- Lubricating oil
- Oil filter, filler and dipstick
- Oil drain lines and valve
-
Mounting System
-
- Rails - Engine/generator/radiator mounting
- Rubber anti-vibration mounts - shipped loose
-
Starting / Charging System
-
- 24 Volt electric starting motor
- Battery and battery rack w/cables
- Battery disconnect switch
-
General
-
- Right hand servicing
- Flywheel and flywheel housing-SAE No. 00
- Paint - Caterpillar yellow with high gloss black rails & radiator
- SAE standard rotation
Optional Equipment:
-
Air Inlet System
-
- Remote air inlet adapters
- Dual element air cleaners
- Air inlet protection
- Heavy duty air cleaners
-
Circuit Breakers
-
- Cable entry options
- Control packaging for enclosures
- Trip units
- Load take off; IEC standard hole
- Busbar power connections
- Center posts busbars
- EMAX breakers
-
Power Termination
-
- Circuit breakers, IEC compliant
-
Control Panels
-
- Annunciator modules
- Generator temperature monitoring
- Auxiliary box
- Remote speed adjust
- Busbar connections
- Vandal proof panel door
- Voltage raise/lower switch
- EMCP 4.3, EMCP 4.4
- Local and remote monitoring
- Language options
- Customer interface options
- External box clips
- EMAX breaker connections
- Governors
-
Cooling System
-
- Heat exchangers
- Water level switch gauges
- Radiator duct flanges
- Optional Serpentine radiators
-
European Certifications
-
- EU Declaration of Conformity
-
Exhaust System
-
- Through wall installation kit
- Muffler mounting kits
- Mufflers
- Flexible fittings
-
Fuel System
-
- Fuel coolers
- Primary fuel filter
-
Generators And Attachments
-
- Generators
- 3 Phase, Random wound, Internal excitation (IE)
- Internal excitation (IE)
- 3 Phase, 380 / 400 / 415 / 3300 / 6600 / 10000 / 10500 / 11000 volt
- Number of leads: 6
- Pitch: 0.6667
-
Instrumentation
-
- Pyrometers and thermocouples
- Thermocouples
-
Lube System
-
- Oil level regulator
- Electric prelube pumps
- Manual prelube sump pumps
-
Mounting System
-
- IBC vibration isolators
- Spring type vibration isolators
-
Protection System
-
- Explosion relief valves
-
Special Tests / Reports
-
- IBC seismic Certification
- CSA test and certification
- PGS Test report @ 1.0 power factor
- Neutral ground certificate
- PGS Test report @ 0.8 power factor
-
Starting / Charging System
-
- 10 and 20 Amp Battery chargers
- Charging alternators - 50 Amp
- Dual 24 volt electric starting motors
- ETHER starting aids
- 24 Volt battery set - Dry
- Jacket water heaters
-
General
-
- Engine barring group