Generator Set Specifications
Maximum Rating
3500 kVA
Minimum Rating
3000 kVA
Emissions/Fuel Strategy
Tier 2 Equivalent - 1808 rpm
Voltage
380 to 11000 volts
Frequency
50 Hz
Speed
1808 rpm
Duty Cycle
Standby, Mission Critical
Engine Specifications
Engine Model
3516E, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
8.46in
Displacement
4765in³
Compression Ratio
14.7:1
Aspiration
ATAAC
Fuel System
Electronic Unit Injection
Governor Type
Ademā„¢5
Generator Set Dimensions
Length - Minimum
353.3in
Length - Maximum
363.1in
Width - Minimum
104in
Width - Maximum
104in
Height - Minimum
132.6in
Height - Maximum
131.6in
Dry Weight - Genset (minimum)
47620lb
Dry Weight - Genset (maximum)
52911lb

Standard Equipment:

Air Inlet System
  • Air cleaner; single element canister type
 
Control System
  • Text alarm/event descriptions
  • Emergency stop pushbutton
  • IVR includes reactive droop capability
  • KVAR / PF modes
  • EMCP 4.2B
  • 3 Phase voltage sensing
  • Generator mounted - rear facing
  • Generator set packages include:
  • 24 Volt DC operation
  • Caterpillar's voltage regulator
  • RFI suppression
  • Environmental sealed front face
  • Limiter and exciter diode monitor
  • Min / max exciter
  • Controls:
  • Speed adjust
  • Alarm acknowledge
  • Auto/start/stop control
  • Engine cycle crank
  • Engine cool
  • Customizable screens
  • PLC functionality
  • Lamp test
  • Load histogram feature
  • Accessory module data link
  • Reverse power (kW) (32)
  • 6 Customer programmable digital inputs
  • 3 Phase
  • +/- 2% accuracy
  • High coolant temperature
  • 0 True RMS AC metering
  • Programmable protective relaying functions:
  • Reverse reactive power (kVAr) (32RV)
  • Communications:
  • Generator phase sequence
  • Over/under voltage (27/59)
  • Overcurrent (50/51)
  • RPM
  • Number of I/O varies on options selected
  • Overspeed
  • Serial annunciator module data link
  • Low coolant temperature
  • 4 Programmable relay outputs (Form A)
  • 1 Programmable relay outputs (Form C)
  • 3 Analog inputs
  • Over/under frequency (81 o/u)
  • Digital indication for:
  • Low coolant level
  • Failure to start (overcrank)
  • Cat connect
  • 1 Programmable digital outputs
  • DC volts
  • Operating hours
  • Coolant temperature
  • Oil pressure (psi, kPa or bar)
  • Amps (per phase & average)
  • Power factor (per phase & average)
  • Frequency (Hz)
  • Volts (L-L & L-N)
  • kW (per phase, average & percent)
  • kVA (per phase, average & percent)
  • kVAr (per phase, average & percent)
  • Warning/shutdown with common LED indication of shutdowns for: Low oil pressure - High coolant temperature - Overspeed - Emergency stop - Failure to start (overcrank) - Low coolant temperature - Low coolant level -
  • Low oil pressure
  • kW-hr (total)
  • kVAr-hr (total)
 
Cooling System
  • ATAAC - 3516E package radiators shipped installed
  • Certified standard PGS provided
 
Exhaust System
  • Flanged faced outlet(s)
  • Dry exhaust manifold
 
Fuel System
  • Secondary fuel filters
  • Fuel cooler; not included with packages without radiator
  • Flexible fuel lines - shipped loose
 
General
  • Right hand servicing
  • Caterpillar yellow with high gloss black rails and radiator
  • SAE standard rotation
  • Flywheel and flywheel housing - SAE No. 00
 
Generator And Attachments
  • NEMA standard hole pattern
  • Medium voltage:
  • Anti-condensation space heater
  • NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
  • Winding temperature detectors
  • High voltage:
  • Busbar connections, right side extension box, bottom cable entry
  • Form wound
  • Low voltage: Random wound - Internal excitation (IE) - Winding temperature detectors - NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby) - Busbar connections, top center mounted, top cable entry - NEMA standard hole pattern
  • 6 Lead
  • Permanent magnet excitation (PMG)
  • 3 Phase brushless, Salient pole
  • Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
 
Governing System
  • ADEM A5
 
Literature
  • Parts book
  • Operation & Maintenance Manual
 
Lubrication System
  • Integral lube oil cool
  • Oil filter, filler and dipstick
  • Oil drain lines and valve
  • Gear type lube oil pump
  • Lubricating oil
  • Fumes disposal
 
Mounting System
  • Rails - Engine/generator/radiator mounting
  • Anti-vibration mounts (shipped loose)
  • Rubber anti-vibration mounts - shipped loose
 
Starting System
  • 24 Volt electric starting motor
  • Battery disconnect switch
  • Battery and battery rack w/cables
  • 45 Amp Charging alternator
 

Optional Equipment:

Control System
  • EMCP 4.4
 
Air Inlet System
  • Single element filter
  • Dual element air cleaner
 
Cooling System
  • Standard ambient radiators
  • Water level switch gauges
  • Optional installed ATAAC radiators
  • Optional installed radiators
  • Coolant
  • Standard ambient ATAAC radiators
 
Crankcase System
  • Ventilation system
  • No explosion relief valves
  • Explosion relief valves
 
Exhaust System
  • Y Adapters
 
Fuel System
  • Fuel priming pumps (Tier 4) - Manual or electric
  • Primary fuel filter
 
General
  • Special paint (Colors other than Caterpillar yellow or high performance paints)
  • US aid emblem
 
Generators And Attachments
  • Space heater
  • Differential current transformers (DCT) 8.7 kV and 15 kV classes
  • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
  • Alternator air cleaner
  • Thermostat for space heater
  • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
  • Generator conversion
 
Instrumentation
  • Pyrometer and thermocouples
 
Lubrication System
  • Oil level regulator
  • Prelube pumps
  • Lube oil in standard sump
 
Mounting System
  • Puck style low efficiency isolators
  • Spring type vibration isolators
  • IBC vibration isolators
 
Power Connections
  • Neutral ground connections
  • Center post busbars
  • Right side power connections
 
Special Tests / Reports
  • Generator set fuel consumption test
  • PGS Test report @ 1.0 power factor
  • Standard engine test charge
  • Canadian Standards Association certification
  • Generator test report
  • IBC Certification
  • OSHPD Certification
  • Fuel consumption test
  • Torsional vibration analysis reports
  • PGS Test report @ 0.8 power factor
 
Starting And Charging
  • Starter cover
  • Air pressure regulator
  • 10, 20, 35 and 50 Amp Battery chargers
  • 24 Volt battery set - Dry
  • Jacket water heaters
  • Air starting motors
  • Electric starting motors
  • Engine barring device
 
Extended Service Coverage
  • Platinum, Gold and Silver coverage
 

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.