C15 Generator Set

C15 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications
Maximum Rating
500 ekW
Minimum Rating
320 ekW
Emissions/Fuel Strategy
Low Fuel, Tier 2, Tier 3, EU Stage IIIA
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 RPM
Duty Cycle
Standby, Prime
Engine Specifications
Engine Model
C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
5.4in
Stroke
6.75in
Displacement
927.56in³
Compression Ratio
16.1:1
Aspiration
Air to Air Aftercooled
Fuel System
MEUI
Governor Type
Ademā„¢A4
Generator Set Dimensions
Length - Maximum
168.2in
Width - Maximum
81in
Height - Maximum
126.3in

Standard Equipment:

Air Inlet
  • Air cleaner
 
Air System
  • Turbocharger
  • Air cleaner - Non canister disposable paper filter
  • Aftercooler core
 
Control Panel
  • GCCP 1.3
  • GCCP 1.3 Genset Controller
 
Cooling
  • Package mounted radiator
 
Cooling System
  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive
  • Radiator and cooling fan with guard
  • Coolant drain line with valve
 
Exhaust
  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied
  • Exhaust flange outlet
 
Fuel
  • Secondary fuel filters
  • Primary fuel filter with integral water separator
  • Fuel priming pump
 
Fuel System
  • Primary fuel filter w/integral water separator and secondary filter
  • Fuel priming pump
  • Engine fuel transfer pump
  • Flexible fuel lines
  • Fuel cooler
 
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • IP23 Protection
 
Power Termination
  • Busbar
 
Generator And Attachments
  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • Integrated voltage regulator (IVR)
  • Segregated low voltage (AC/DC) wiring panel
  • Optional LC Frame generator - IP23 Protection
  • Power center, IP22
  • A Frame generator - IP21 Protection
 
Mounting
  • Rubber vibration isolators
 
Governing System
  • Cat electronic governor (ADEM A4).
 
Lube System
  • Oil cooler
  • Oil drain valves
 
Mounting System
  • Captive linear vibration isolators between base and engine-generator includes lifting provisions and termination points for coolant and lube oil drain lines
 
Starting/charging
  • 24 Volt battery with rack and cables
  • 24 volt starting motor
  • Batteries
 
General
  • Engine and alternator pre paint, Caterpillar yellow
  • Paint - Caterpillar yellow except rails and radiators gloss black
 

Optional Equipment:

Air Inlet System
  • Single element air cleaner
  • Dual element air cleaner
 
Exhaust
  • Industrial, residential, critical mufflers
 
Certifications
  • EU Certificate of Conformance (CE)
  • Global certification for CIS
 
Circuit Breakers
  • Shunt trip for IEC circuit breaker
  • Padlockable circuit breaker device
  • 4 Pole (IEC-100% rated) Circuit breakers - Motorised
  • Auxiliary contacts, circuit breaker
  • 3 Pole (IEC-100% rated) Circuit breakers - Motorised
  • 3 Pole (IEC-100% rated) Circuit breakers - Package mounted
  • 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
  • Power terminal strip
 
Generator
  • Oversize and premium generators
  • Anti-condensation heater
  • Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
 
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
 
Control Panels
  • GCCP 1.4
  • Volt free contacts
  • Local annunciator
  • Remote annunciator module
  • Local alarm horn
  • Oil temperature displays
  • Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
 
Starting/charging
  • Jacket water heater
  • Charging alternator
  • Heavy duty starting system
  • Battery chargers
  • Oversize batteries
 
Cooling System
  • Stone guards
  • Radiator duct flange
  • Low coolant temperature alarm
 
Enclosures
  • Sound attenuated enclosures
  • High ambient sound attenuated enclosures
 
General
  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • CSA Certification
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • EEC Declaration of Conformity
  • Integral & sub-base UL listed dual wall fuel tanks
  • Automatic transfer switches (ATS)
  • Single or dual wall sub-base fuel tanks
  • The following options are based on regional and product configuration:
  • EU Certificate of Conformance (CE)
  • Single or dual wall integral fuel tanks
  • Narrow, wide or skid base
  • UL 2200 package
 
Exhaust System
  • Engine mounted muffler
  • End in/end out mufflers - 10, 25 and 35 dBA attenuation
  • 6 and 8 inch elbow kit
  • Manifold and turbocharger guards
  • Flexible exhaust fittings
  • 6 and 8 inch flange GP
 
Fuel System
  • Manual fuel transfer pump
  • Dual wall fuel tank base
  • Fuel transfer system controls
 
Generator And Attachments
  • Space heaters
  • Permanent magnet excitation (PMG) generator
  • Ingress protection
  • LC frame generator
  • Oversize A Frame generator
  • LC frame CIP generator
  • CIP A Frame generator
  • Oversize LC frame generator
 
Lube System
  • Manual sump pump
 
Mounting System
  • Narrow skid base - replaces standard fuel tank base
 
Special Test / Reports
  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor
 
Starting / Charging System
  • 5 Amp single Battery charger
  • Battery disconnect switch
  • Jacket water heater
 

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.