C18 Generator Set - Thompson Tractor

C18 Generator Set

C18 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications
Maximum Rating
750 ekW
Minimum Rating
500 ekW
Emissions/Fuel Strategy
U.S. EPA Certified
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime
Engine Specifications
Engine Model
Cat® C18 ATAACTM In-line 6, 4-cycle diesel
Bore
5.71in
Stroke
7.2in
Displacement
1106.3in³
Compression Ratio
14:01
Aspiration
Turbocharged Air to Air Aftercooled
Fuel System
Electronic unit injection
Governor Type
Electronic ADEM™ A4
Generator Set Dimensions
Length - Maximum
138in
Width - Maximum
67in
Height - Maximum
88in

Standard Equipment:

Air Inlet System
  • Aftercooler core
  • Turbocharger
 
Control System
  • 3 Pole
  • GCCP 1.2
  • Right mounted power centre
  • Standard breaker
 
Cooling System
  • Jacket water pump, gear driven, centrifugal
  • Thermostats and housing
  • Coolant level sight gauge
  • Coolant level sensor
  • Coolant drain valve; terminated on edge of base
  • Cooling system filled with Caterpillar extended life coolant
  • Radiator and cooling fan with belt guards
 
Exhaust System
  • Exhaust manifold - dry
 
Fuel System
  • Primary fuel filter w/integral water separator and secondary filter
  • Flexible fuel lines
  • Fuel cooler
  • Engine fuel transfer pump
  • Fuel priming pump
 
Generator And Attachments
  • Brushless, self-excited 2/3 pitch, random wound
  • Insulation Class H and temperature rise
  • Power centre, IP22 bottom cable entry
  • Segregated low voltage wiring panel
  • IP23 Protection
 
Mounting System
  • Anti-vibration mounts (Non-captive)
  • Generator mounting and duct pPlate
  • Narrow skid base
 
Protection System
  • Overspeed
  • Low oil pressure shutdown
  • High coolant temperature shutdown
  • Low coolant level shutdown
 
Starting/charging
  • 24 Volt electric starting motor
 

Optional Equipment:

Air Inlet System
  • Dual element air cleaner
  • Heavy duty canister air filters
 
Control System
  • Annunciators box
  • Volt free contact
  • Remote E-Stop button
  • Discrete I/O module
  • Earth (Ground) fault relay
  • Local annunciator
  • GCCP 1.5
 
Circuit Breakers
  • Auxiliary contacts
  • Neutral bar (208V)
  • Single LSI motorised circuit breaker
  • Single LSI motorised circuit breaker
  • External paralleling
 
Enclosures
  • Sound attenuated (SA)
  • Weather protective
  • Aluminum enclosure
 
Cooling System
  • Stone guards
  • Coolant heater
  • Jacket water heater with pump
 
Base / Fuel Tank
  • Audio & visual fuel alarm
  • Sub Base Dual Wall Fuel Tank: 660, 1000, 1900, 2200 gal
 
Fuel System
  • Sub tank bases: 24 hr & 48 hr
  • Integral 8 hour tank base
 
Generator And Attachments
  • LC frame oversize generators
  • Space heater control
  • PMG, AREP
  • Oversize
  • Coastal protection (CIP)
 
Starting And Charging
  • Battery disconnect switch
  • 5 Amp Battery charger
  • Oversize battery set
  • Standard battery set
 
Certifications
  • Certification of Compliance � IBC
  • CSA 22.2
  • Dual IBC & OSHPD
  • UL2200 Listed
  • Seismic
 
General
  • Tool set
 
Lube System
  • Manual sump pump
 

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.