Cat EGP Switchgear

Cat EGP Switchgear

Cat EGP Switchgear

EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source.

Technical Summary
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation
Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application
LV and MV (208V - 38 kV)
Generator Protective Devices
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51
Environmental Parameters
Certifications
IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R Freestanding Construction
Operating Temperature
0°C to 50°C
Storage Temperature
-20°C to +60°C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Standard Equipment:

Egp Switchgear
  • Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
  • Emergency Stop Button for each generator
  • Instant Auto Switch
  • Generator Demand Priority Control
  • Audible Alarm & Horn Silence Button
  • Circuit Breaker Control Switch with Indicators
 

Optional Equipment:

Data Table Interface
  • * Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
 
Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
  • * Provides additional discrete synchronization protection
 
Remote Power Monitoring System
  • * To monitor breaker status, alarms, metering and other operating parameters
 