D600 GC (60 Hz) Generator Set
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
-
Generator Set Specifications
-
- Maximum Rating
- 600 ekW
- Minimum Rating
- 600 ekW
- Emissions/Fuel Strategy
- EPA Stationary Emergency
- Voltage
- 480 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby
-
Engine Specifications
-
- Engine Model
- CatĀ® C18 In-line 6, 4-cycle Diesel
- Bore
- 5.7in
- Stroke
- 7.2in
- Displacement
- 1106in³
- Compression Ratio
- 14.5:1
- Aspiration
- Turbocharged Air-to-Air Aftercooled
- Fuel System
- MEUI
- Governor Type
- ADEMā¢A4
-
Generator Set Dimensions
-
- Length - Maximum
- 196.1in
- Width - Maximum
- 73.4in
- Height - Minimum
- 79.1in
- Height - Maximum
- 100.9in
- Dry Weight - Genset (minimum)
- 8959.6lb
- Dry Weight - Genset (maximum)
- 11647lb
Standard Equipment:
-
Air Inlet System
-
- Turbocharger
- Air cleaner - Non-Canister, Disposable
- Aftercooler core
-
Control Panel
-
- GCCP 1.2
-
Cooling System
-
- Radiator sight gauge
- Thermostats and housing.
- Coolant drain valve.
- Jacket water pump, gear driven, centrifugal
- Blower fan and fan drive with guards
- Radiator, Package mounted.
-
Exhaust System
-
- Exhaust manifold; dry
-
Fuel System
-
- Fuel cooler
- Primary fuel filter w/integral water separator and secondary filter, spin on
- Integral Tank Base, 24 Hrs, UL142
- Engine fuel transfer pump
- Fuel priming pump
-
Generator Set
-
- Complete system designed & built at ISO 9001:2000 certified facilities
- Factory tested to design specifications at full load conditions
- All protective devices and control functions simulated and checked
-
Generators And Generator Attachments
-
- 6 leads
- Voltage regulator (single phase sensing)
- Easy access to AVR and terminals
- Insulation, Class H
- Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
- Terminal Box, IP22 RHS Facing, Bottom Cable Entry
- Standard winding protection for non-harsh environments with relative humidity ? 95%
- IP23 protection
-
Governing System
-
- Cat Electronic Governor (ADEM A4)
-
Lube System
-
- Oil filler and dipstick.
- Shallow oil pan.
- Oil filter, spin on.
- Oil cooler
- Lubricating Oil, CK-4 (10W-30)
- Oil drain with valve.
- Fumes disposal to front of radiator.
-
Mounting System
-
- Includes lifting provisions and termination points for coolant and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator
-
Protection
-
- Safety Shutoff - High water temperature
- Safety Shutoff - Overspeed
- Safety Shutoff - Low Oil Pressure
-
Starting/charging System
-
- 24V,45 amp charging alternator.
- 24-volt electric starting motor.
-
General
-
- Parts Book
- Vibration damper.
- Lifting Eyes
Optional Equipment:
-
Air Inlet System
-
- Air Cleaner (Non-Canister Disposable)
-
Bases, Mounting & Fuel Tanks
-
- Audio & Visual Fuel Alarm (@90% Fuel Level)
- Integral Tank Base, 24 Hrs, UL142
- 5 gallon Spill Containment
- Overfill Prevention Valve
- Fuel Tank Fill Pipe & Lockable Cap
- Wide Base - Skid
-
Circuit Breaker
-
- 400A LSI
- Auxiliary Contacts
- 400A LS/I
- 800A LSI
- 600A LSI
- 1200A LS/I
- 800A LS/I
- 600A LS/I
- 1200A LSI
-
Control System
-
- 20A GFCI (Ground Fault Circuit Interrupter)
- Ground Fault Relay
- 16 -light NFPA 99/110 Annunciator
- Volt Free Contacts
- Twist Release, Red Button Emergency Stop
- 100A Load Center
- Product Link Remote Monitoring hardware
- Audible Alarm Gp
- Earth (Ground) fault relay
- Volt free contact
- Remote E-Stop button
- Discrete I/O module
- Annunciators box
- Local annunciator
-
Exhaust System
-
- 8" Muffler - 25 dBA Attenuation
- Flexible Exhaust Connection
- Manifold & Turbocharger Guards
-
Generator
-
- Space Heater
- Permanent Magnet Generator
-
Starting System
-
- Jacket Water Heater
- Standard Battery Set: 1000 CCA, 90 amp/hr.
- Battery Charger (UL Certified)
- Oversize Battery Set, 1400 CCA, 200 amp/hr.
-
General
-
- Extended Service Coverage
- Generator Test Report
- CSA Certification
- UL2200 Certification
- Tool set
-
Circuit Breakers
-
- Single LSI motorised circuit breaker
- Single LSI motorised Circuit Breaker
- Auxiliary contacts
- Neutral bar (208V)
-
Enclosures
-
- E-Stop
- Sound Attenuated Level 2 Enclosure (White)
- AC & DC Source Lights
- Sound attenuated enclosure
-
Cooling System
-
- Coolant heater
- Stone guards
- Jacket water heater with pump
-
Base / Fuel Tank
-
- Audio & visual fuel alarm
-
Fuel System
-
- Integral 8 hr tank base
-
Starting And Charging
-
- Oversize battery set
- Standard battery set
- 5 Amp battery charger
- Battery disconnect switch
-
Certifications
-
- CSA 22.2
- UL2200 Listed
- Seismic
-
Lube System
-
- Manual sump pump