Generator Set Specifications
Maximum Rating
150 kVA
Minimum Rating
150 kVA
Emissions/Fuel Strategy
Non Regulated
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
C7.1 I-6, 4-Cycle Diesel
Bore
4.1in
Stroke
5.3in
Displacement
427.8in³
Compression Ratio
18.2:1
Aspiration
Turbocharged
Fuel System
Inline
Governor Type
Mechanical
Generator Set Dimensions
Length - Maximum
130.9in
Width - Maximum
44.6in
Height - Maximum
65.6in
Dry Weight - Genset (maximum)
4043lb

Standard Equipment:

Engine
  • C7.1, Inline 6 cylinder, 4 stroke diesel
 
Control Panels
  • GCCP 1.1
 
Enclosure
  • Cat GC enclosure
 
Governor
  • Mechanical governor
 
Fuel Storage
  • Single wall 8 hour fuel tank
 
Alternator
  • A Frame standard alternator
 
Air, Cooling & Exhaust
  • Enclosure silencer
 
General
  • Engine and alternator pre-paint, Caterpillar yellow
 

Optional Equipment:

Certification
  • Certificate of Conformance
  • Australia, CIS, Gulf Certification
 
Auxiliary Supply Voltage
  • 120V
 
Alternator Requirements
  • Space heater
 
Genset Control
  • Volt free contacts for common alarm
  • Battery charger
  • Panel mounted audible alarm
  • Volt free contacts for genset running
  • Earth leakage
  • Earth fault
  • Emergency stop with key
  • USB to RS485 Communications device
  • Coolant heater
  • Battery
  • Low coolant level shutdown
 
Fuel Storage
  • Dual wall 8 hour fuel tank
  • Low fuel level shutdown
  • Low fuel level alarm
  • Single wall tank with containment
  • High fuel level alarm
 
Circuit Breaker
  • 3 Pole Circuit breaker 630A
  • 4 Pole Circuit breaker 250A
  • 4 Pole Circuit breaker 200A
  • 3 Pole Circuit breaker 200A
  • 3 Pole Circuit breaker 250A
  • 4 Pole Circuit breaker 400A
  • 4 Pole Circuit breaker 630A
  • Circuit breaker padlock
  • Neutral earth link
  • Overload via alarm switch on breaker
  • 3 Pole Circuit breaker 400A
 
Testing & Packaging
  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8PF
 