Generator Set Specifications
Maximum Rating
660 kVA
Minimum Rating
660 kVA
Emissions/Fuel Strategy
Non Regulated
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
C15 In-line 6, 4-cycle diesel
Bore
5.4in
Stroke
6.8in
Displacement
928in³
Compression Ratio
16.1:1
Aspiration
Turbocharged Air-to-Air Aftercooled
Fuel System
EUI
Governor Type
Ademā„¢A4
Generator Set Dimensions
Length - Maximum
131in
Width - Maximum
60.6in
Height - Maximum
86.1in
Dry Weight - Genset (maximum)
8364lb

Standard Equipment:

Engine
  • Cat® C15 Inline 6 cylinder, 4 stroke diesel
 
Air Inlet
  • Air cleaner
 
Control Panels
  • GCCP 1.1
 
Governor
  • Mechanical governor
 
Cooling
  • Package mounted radiator
 
Alternator
  • A Frame standard alternator
 
Fuel Storage
  • Single wall 8 hour fuel tank
 
Cooling System
  • Radiator and cooling fan with guards
  • Fan drive, battery charging alternator drive
 
Fuel
  • Fuel priming pump
  • Primary fuel filter with integral water separator
  • Secondary fuel filters
 
Electrical Options
  • 3 Pole Circuit breaker
  • Neutral earth link
  • 24 Volt battery with rack and cables
 
Air Inlet System
  • Air cleaner; light duty with disposable element
 
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • IP23 Protection
 
Lube System
  • Lubricating oil
  • Oil drain line with valve
 
Mounting System
  • Captive linear vibration isolators
  • Lifting provision and drag points
 
General
  • Engine and alternator pre paint, Caterpillar yellow
  • Engine and alternator pre paint, Caterpillar yellow
 
Power Termination
  • Busbar
 
Generator And Attachments
  • Power center, IP22
  • Segregated low voltage (AC/DC) wiring panel
  • Optional LC Frame generator - IP23 Protection
  • Integrated voltage regulator (IVR)
  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
 
Mounting
  • Rubber vibration isolators
 
Governing System
  • Cat electronic governor (ADEM A4).
 
Lube System
  • Oil cooler
  • Oil drain valves
 
Mounting System
  • Captive linear vibration isolators between base and engine-generator includes lifting provisions and termination points for coolant and lube oil drain lines
 

Optional Equipment:

Control Panel
  • PLG 4G/3G/Ethernet
  • Annunciator
  • Emergency E-Stop
 
Exhaust
  • Industrial, residential, critical mufflers
 
Enclosure
  • Cat GC enclosure
 
Generator
  • Oversize and premium generators
  • Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
  • Anti-condensation heater
 
Electrical Options
  • 4 Pole Circuit breaker
  • Auxiliary contacts
  • Padlockable circuit breaker
  • Battery charger
  • Wet battery
 
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
 
Alternator
  • Space heater
  • AVR
 
Generator And Attachments
  • Oversize A Frame generator
  • LC frame generator
  • LC frame CIP generator
  • Ingress protection
  • CIP A Frame generator
  • Permanent magnet excitation (PMG) generator
  • Oversize LC frame generator
  • Space heaters
 
Starting/charging
  • Oversize batteries
  • Charging alternator
  • Jacket water heater
  • Battery chargers
  • Heavy duty starting system
  • 24 Volt battery with rack and cables
 
Air Inlet System
  • Single stage air filter
  • Dual element air filter
 
Certifications
  • EU Certificate of Conformance (CE)
  • EAC Certification
 
General
  • The following options are based on regional and product configuration:
  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • UL 2200 package
  • CSA Certification
  • Narrow, wide or skid base
  • EEC Declaration of Conformity
  • EU Certificate of Conformance (CE)
  • Single or dual wall sub-base fuel tanks
  • Single or dual wall integral fuel tanks
  • Automatic transfer switches (ATS)
  • Integral & sub-base UL listed dual wall fuel tanks
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
 
Extended Service Coverage
  • 3, 4, 5 and 10 Years
 
Enclosures
  • High ambient sound attenuated enclosures
  • Sound attenuated enclosures
 
Exhaust System
  • Industrial silencer
  • 10 dBA Attenuation silencer
  • 6 and 8 inch elbow kit
  • Flexible exhaust fittings
  • 6 and 8 inch flange GP
  • Manifold and turbocharger guards
  • End in/end out mufflers - 10, 25 and 35 dBA attenuation
  • Engine mounted muffler
 
Fuel System
  • Dual wall 8 hour fuel tank
  • Single wall 8 hour fuel tank with spill containment
  • Low fuel level shutdown
  • Low and high fuel level alarms
  • Manual fuel transfer pump
  • Dual wall fuel tank base
  • Fuel transfer system controls
 
Lube System
  • Manual sump pump
 
Mounting System
  • Narrow skid base - replaces standard fuel tank base
 
Special Test / Reports
  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor
 
Starting / Charging System
  • 5 Amp single Battery charger
  • Jacket water heater
  • Battery disconnect switch
 

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.