Generator Set Specifications
-
- Maximum Standby Rating
-
500 ekW @0.8pf
- Fuel Type
-
Natural Gas
- Emissions/Fuel Strategy
-
U.S. EPA Certified for Emergency Only Stationary Genset
- Frequency
-
60 Hz
- RPM
-
1800 rpm
-
Engine Specifications
-
- Engine Model
-
G3412
- Displacement
-
1649in³
- Aspiration
-
NA
- Bore
-
5.4in
- Stroke
-
6in
-
Generator Set Dimensions
-
- Length
-
165in
- Width
-
85.25in
- Height
-
86in
- Dry Weight - Genset
-
14700lb
Standard Equipment:
-
Air Inlet
-
- Two-element single-stage air cleaner with enclosure and service indicator
- Dual air cleaners, 1 per side, with service indicator
-
Control Panel
-
-
Cooling
-
- Package mounted radiator
- LH or RG connections when radiator is not selected
- Engine driven pumps for jacket water and separate circuit aftercooler
- Jacket water and SCAC thermostats
-
Fuel
-
- Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
- Gas Train: NFPA37 and CSA B149.3
-
Exhaust
-
- Dry exhaust manifolds, insulated and shielded
-
Fuel System
-
- Engine-installed electronic control valve
- Gas pressure regulator
- 24V DC energized-to-run (ETR) gas shutoff valve
-
General
-
- Paint- Caterpillar Yellow with gloss black rails and radiators
- Operation and maintenance manuals
- RH Service
- Parts book
- Crankshaft vibration damper and guard
-
Lubrication
-
- Cartridge style oil filter
- Gear type lube oil pump
-
Generator
-
- Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
- Anti-condensation space heater
- Permanent Magnet Excitiation
- Winding temperature detectors
-
Governing System
-
-
Ignition System
-
- Electronic Ignition System (controlled by ADEM A4)
- Individual Cylinder Detonation Sensitive Timing (DST)
-
Starting/charging
-
- Electric Starter
- 24V DC starting motors
Optional Equipment:
-
Air Inlet
-
- Air cleaner with precleaner
-
Circuit Breakers
-
- S LSI
- Frame mounting
- Right, left, rear mounted
-
Control Panel
-
- Local alarm module
- Local PC monitoring
- Remote PC monitoring
- Remote annunciator
-
Cooling
-
- Inlet/Outlet connections
- Coolant level drain line with valves, fan with guard
-
Exhaust
-
- Flexible fittings
- 15, 25 dBA Attenuation
-
General
-
- Digital diagnostic tool
- Tool set
- US AID emblem
-
Generator
-
- Cable access box
- Bearing temperature detectors
-
Starting/charging
-
- Battery with cables and rack (shipped loose)
- 10A, 24VDC battery charger
- Jacket water heater