Generator Set Specifications
-
- Gas Standby Rating
-
1000 ekW @ 0.8pf
- Fuel Type
-
Natural Gas
- Emissions/Fuel Strategy
-
U.S. EPA Certified for Non-Emergency Stationary Genset
- RPM
-
1800 rpm
- Frequency
-
60 Hz
- Compression Ratio
-
9.7
- Displacement
-
3173in³
-
Engine Specifications
-
- Engine Model
-
G3512
- Displacement
-
3173in³
- Aspiration
-
TA
- Bore
-
6.7in
- Stroke
-
7.5in
-
Generator Set Dimensions
-
- Length
-
205.7in
- Width
-
90in
- Height
-
99.4in
- Weight
-
27500lb
Standard Equipment:
-
Air Inlet
-
- Two-element single-stage air cleaner with enclosure and service indicator
- Dual air cleaners, 1 per side, with service indicator
-
Control Panel
-
-
Cooling System
-
- Engine driven pumps for jacket water and separate circuit aftercooler
-
Cooling
-
- Package mounted radiator
- Jacket water and SCAC engine-driven pumps
- Jacket water and SCAC thermostats
- LH or RG connections when radiator is not selected
-
Exhaust
-
- Dry exhaust manifolds, insulated and shielded
- Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
- Cat-flanged face outlet on turbocharger
-
Fuel
-
- NOx sensor based air-fuel-ratio control
- Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
- Gas Train: NFPA37 and CSA B149.3
- 0.5 to 5 psi engine fuel inlet pressure
-
Fuel System
-
- Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
- Engine-installed electronic control valve
- Throttle plate, 24V DC actuator, controlled by GECM
- 24V DC energized-to-run (ETR) gas shutoff valve
- Gas pressure regulator
-
General
-
- Operation and maintenance manuals
- Paint- Caterpillar Yellow except rails and radiators gloss black
- Parts book
- “Stationary Use Only” Label in Correspondence with EPA Nonroad Mobile SI rule
- RH Service
- Crankshaft vibration damper and guard
-
Lubrication
-
- Cartridge style oil filter
- Gear type lube oil pump
-
Starting/charging
-
- Jacket water heater
- Battery with cables and rack (shipped loose)
- Electric Starter
- Batteries with rack and cables
- 24V DC starting motors
-
Generator
-
- NEMA Class H insulation
- Permanent Magnet Excitiation
- SR5
- Anti-condensation space heater
- Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
- Winding temperature detectors
-
Ignition System
-
- Electronic Ignition System (controlled by ADEM A4)
- Individual Cylinder Detonation Sensitive Timing (DST)
-
Governing
-
- ADEM A4 speed governor with 4 to 20ma (0V to 5V) speed input
Optional Equipment:
-
Air Inlet
-
- Mounting brackets and piping
- Air cleaner with precleaner
-
Control Panel
-
- Local PC monitoring
- Engine failure relay
- Remote PC monitoring
- Local alarm module
- Remote annunciator
-
Cooling
-
- Remote radiator for JW and SCAC circuits, level switch included but not wired
- Inlet/Outlet connections
- Coolant level drain line with valves, fan with guard
-
Circuit Breakers
-
- 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
- Frame mounting
- S LSI, G LSIG, P LSIG-P, 4th Digit Type
- Right, left, rear mounted
- 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
- 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
- 3-pole (IEC 947-2 rated)
- 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
-
Exhaust
-
- 305 mm (12 in.) flange
- Flexible fittings
- 18, 25 dBA Attenuation
- 305 mm (12 in.) muffler
- 305mm (12 in) spark arresting muffler
- 305 mm (12in.) elbow
-
Fuel System
-
- 3, 0-100 kPag, 4-20mA gas train pressure sensors
-
General
-
- US AID emblem
- Special paint order
- Digital diagnostic tool
- Tool set
-
Generator
-
- Generator air filter
- European bus bars
- Low voltage extension box
- Cable access box
- Bearing temperature detectors
-
Starting/charging
-
- 20A, 24VDC battery charger
- 24V starting motors