3512B Offshore Generator Set - Thompson Tractor

3512B Offshore Generator Set

3512B Offshore Generator Set

3512B Offshore Generator Set

Cat 3500 offshore generator sets are specifically designed for drilling and production operations offshore. Decades of experience powering offshore vessels and platforms make have evolved into a product that offers proven performance, low emissions, high durability, and low owning and operating costs.Applications for 3500 offshore generator sets include main power, essential services power, and emergency power on-board drilling and production rigs and vessels.Cat generator sets are backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty.Cat 3512B offshore generator set. Ratings: 880-1360 ekW (1100-1943 kVA) @ 50/60 Hz (1000/1200/1500/1800 rpm). Meets IMO Tier I emission standards equivalent. Select ratings meet IMO Tier II emission standards.

Engine Specifications
Minimum Rating
1100kV·A
Maximum Rating
1943kV·A
Emissions
IMO Tier I
Weight
33014lb
Stroke
7.5in
Displacement
3175in³
Bore
6.7in
Oil Change Interval
1000h
Engine Control
ADEM A3
Aspiration
Turbocharged-Aftercooled
Fuel System
EUI
Dimensions
Height
86.9in
Length
190.6in
Width
78.3in
Capacity for Liquids
Cooling System - Engine
106gal (US)
Lube Oil System - Refill
84gal (US)

Standard Equipment:

Air Inlet System
  • Separate Circuit aftercooler core, corrosion resistant coated(air side)Air cleaner, regular dutyDual Turbochargers, 152 mm (6 in) OD straight connection
 
Control System
  • Caterpillar A-III Electronic Engine Control, LHwith Electronic Unit Injector Fuel SystemRigid Wiring Harness(10 amp DC power required to drive Electronic Engine Control Module)
 
Cooling System
  • Outlet controlled thermostat and housing, full opentemperature 92°C (198°F)
  • Jacket water pump, gear driven
  • Single water outlet connection, includes flange:143 mm (5.6")
  • Aftercooler fresh water cooling pump (SCAC), gear drivencentrifugal
  • SCAC pump circuit contains a thermostat to keep theaftercooler coolant from falling below 30°C (85°F)
 
Exhaust System
  • Dry gas tight exhaust manifolds with heat shieldsDual Turbochargers with watercooled bearings and heat shieldsExhaust outlet, vertical, 203 mm (8 in) round flanged outlet
 
Flywheels & Flywheel Housings
  • Flywheel, SAE No. 00, 183 teethFlywheel housing, SAE No. 00
 
Fuel System
  • Fuel filter
  • Fuel transfer pump
  • Electronically Controlled Unit Injectors
  • Fuel priming pump, LH
  • Rigid fuel return line with customer connection point asbase of engine
 
Instrumentation
  • Overspeed shutdown notification light, Emergency stop notification light
  • Graphical Unit (Marine Power Display) for analog or digital displayof:
 
Lube System
  • Crankcase breather, top mounted
  • Oil cooler
  • Oil filter and dipstick, LH
  • Oil pump, gear-type
  • Oil pan drain valve, 2" NPT female connection
 
Protection System
  • A-III Electronic Monitoring System provides customer programmableengine de-ration strategies to protect against adverse operatingconditions
  • Emergency stop push button (located in Electronic Instrument Panel)Safety shutoff protection:
 
Starting System
  • Air starting motor, RH, 620 to 1034 kPa (90 to 150 psi),LH control
  • Air silencer
 
General
  • Paint, Caterpillar yellow, with black rails
  • Vibration damper and guard
  • Lifting eyes
  • Engine and generator, three-point mounted to sub-base
  • Lift provisions on base
  • Oil drain extension
  • Engine length drip pan
 

Optional Equipment:

Air Inlet System
  • Remote Air Inlet Adapters
 
Charging System
  • Battery Chargers
  • Charging Alternators
 
Control System
  • Load Sharing module
  • Local speed throttle control
  • Direct rack control interface, 0-200 mA DC control
 
Cooling System
  • Coolant level sensors
  • Connections
  • Air separator
 
Exhaust System
  • Flexible fittings
  • Elbows
  • Flanges
  • Flange and exhaust expanders
  • Mufflers
 
Fuel System
  • Fuel Cooler
  • Primary fuel filter
  • Fuel filters
  • Duplex fuel filters
  • Fuel level switch
 
Generator Attachments
  • Air filter — generator
  • Bearing temperature detectors
  • Cable access box
  • Manual voltage control
 
Instrumentation
  • PL1000T Communication Module
  • PL1000E Communication Module
  • Customer Interface Box
  • Remote panel display
  • Remote cylinder temperature display
  • Exhaust temperature thermocouples
  • Discrete I/O module
  • Intake manifold temperature sensors
  • Oil temperature sensor
 
Lube System
  • Duplex oil filter
  • Bypass centrifugal oil filter
  • 500-hour oil pan
  • Emergency lube oil connections
  • Oil level regulator
  • Prelube
  • Sump pump
 
Mounting System
  • Vibration isolators
 
Power Take-offs
  • Auxiliary drive shafts and pulleys
 
Starting System
  • Air or electric starting motor
  • Redundant start with select switch
 
Protection System
  • Spray shielding
  • Crankcase explosion relief valve
  • Metal particle detector
 
General
  • Jacket water heater
 

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.